JB-QG-F11 Fire Alarm Controller (Interlocking)
JB-QG-F11 Fire alarm control units (linkage type)
key word:
Enclosure:

Hotline:
- Details
- Structure Size
- Performance
-
- Commodity name: JB-QG-F11 Fire Alarm Controller (Interlocking)
JB-QG-F11 Fire alarm control units (linkage type)
JB-QG-F11 Fire alarm controller (coupling) is a fire alarm controller standard GB 4717-2005, GB 16806-2006 "fire linkage control system" standard, GB/T 19001-2008 "Quality Management system requirements" and "fire products 3C Certified Implementation Rules for fire alarm controllers. It is suitable for centralized system management of fire protection in large shopping malls, living quarters, production bases, office buildings, shopping malls, hotels and other areas.
The equipment adopts modular design, high reliability, strong function, easy maintenance, easy to expand. Man-machine interface using touch screen interface intuitive, easy to use, with good interaction. It is a cabinet type structure.
Equipment composition: 8-inch TFT LCD panel, main engine enclosure, micro thermal printer, battery pack, cabinet.
Main Features
JB-QG-F11 fire alarm controller (coupling) provides 24 detection loops, each loop is connected to a maximum of 239 address devices, the maximum capacity of a single machine 5736 points.It can be used as the centralized machine of the fire alarm monitoring system. The whole system can connect up to 128 fire alarm controllers.
Supports the graphical display function, through the graphical display can be more intuitive real-time observation of the corresponding status of each point.
The embedded real-time system based on 32-bit ARM processor has the characteristics of strong real-time, high reliability, modular design and so on.
8 inch TFT true color industrial LCD screen, with wide temperature range, strong anti-interference ability and other advantages.
Graphical interface, convenient and flexible touch screen operation, better human-computer interaction.
With the black box function, can store 1024 fire records, 1024 fault records.
Powerful external communication function, providing GPRS, Ethernet, CAN, RS485, optical fiber and other communication interfaces.
It has one passive alarm signal output terminal and one passive fault signal output terminal.
Supports the backup function, which automatically implements active/standby power switchover and intelligent battery charge/discharge management.
Key words:- Fire alarm controller (interlocking)
-
-
System capacity 734208 Maximum networked node of the system 128 Single capacity 5736 Maximum number of circuits 24 Maximum number of loop points 239 Liquid crystal display 8-inch TFT True color LCD Touch screen Support Maximum number of points on bus linkage control disk 512 Maximum number of points on multi-line linkage control disk 127 Direct output number 1 public fire passive output and 1 public fault passive output External output power supply 28V(1A) Networking Optional Optical fiber Optional Printer 1 Communication interface CAN 1 RS485 1 GPRS 1 Ethernet 1 USB 1 Power supply Main power AC220(187 ~ 242V) 50Hz Battery Two 12V/38Ah batteries Linkage power supply 12V/17Ah battery (two,10A) , 12V/24Ah battery (two,20A) Loop output voltage DC15V ~ 20V Maximum loop output current 200mA Short circuit protection current 400mA Operating environment temperature 0℃ ~ 45 ℃ Ambient humidity ≤ 95%RH(40± 2 ℃ & NBSP;) Structure dimensions (length * width * height) 600mm× 500mm× 1800mm
Previous
Previous
Provide solutions to your questions and prepare for your choices
Recommended Products
JB-QB-F13 Fire Alarm Controller (Interlocking)
JB-QB-F13 Fire alarm controller (linkage type)
More +Jty-gm-d 12-point optical smoke detector
JTY-GM-D12 Smoke detector-Point detectors using scattered light,Trans mitteil
More +