- Commodity name: JB-QB-F61 type fire alarm controller /F61G type gas fire extinguishing controller
JB-QB-F61 Fire alarm control units /F61G Gas fire extinguishing controller
JB-QB-F61/ JB-QB-F61G is an intelligent two-bus automatic fire alarm equipment which combines fire alarm and gas fire extinguishing. It adopts Chinese liquid crystal display, has one detection loop, the maximum address number is 100 points, and two-zone gas fire extinguishing output. Mainly for medium and small fire engineering project design. Meet GB 16806-2006 "Fire Linkage Control System", GB 4717-2005 "Fire Alarm Controller", GB/T 19001-2008 "Quality Management System requirements" and "Fire products 3C certification Implementation Rules". The equipment environmental protection and safety in line with national standards, safe and reliable.
Main Features
● On-site AC 220V power supply.● Can be through two buses (primary) with 100 probes (or modules or coding sound and light alarm), with one no coding sound and light.
● Contains one public fire alarm, one public fault relay (no fault detection), 24V output (1A in total, available for coding acousto-optic alarm or module, if the current exceeds the need for external field linkage power supply), CAN network output, two cylinders control output (continuous 2A maximum), two answer terminals.
● The maximum input power consumption of the machine is 120W. The battery uses two 12V/4.5AH batteries, which can be used for not less than 8 hours under normal monitoring conditions.
● The controller uses 128*64 lattice liquid crystal, Chinese display, can be programmed simple logic 128 (including logic and, logic or, continuous M in any 2).
●LED lights show critical status. Key operation is divided into three passwords, which can store fire alarms, 1024 records, and 256 records of shielding and operation.
● Printing function, configure serial Chinese micro printer, and according to user needs, select the content of printing.
-
-